Series 616KD Differential Pressure Transmitter
One-Touch® Digital Push-Button Calibration Technology, ±0.25, ±1, or ±2% Accuracy
The Series 616KD Differential Pressure Transmitters with One-Touch® Digital Push- Button Calibration Technology are designed for simplicity, making them the ideal choice for installers and maintenance professionals. These instruments not only alleviate cumbersome turn pots typically found in most transmitters, but eliminate entirely the need to span the instruments during calibration. With a single digital push button, both ZERO AND SPAN are calibrated properly, nothing else is required. No additional reference pressure sources or separate calibration devices are necessary.
NIST CALIBRATION available in Product Configurator.
Product Applications
- Air handlers
- Duct pressure
- Variable air volume
- Filter monitoring
Models & Ordering
Specifications
- Service:
- Air and non-combustible, compatible gases.
- Wetted Materials:
- Consult factory.
- Accuracy:
- 616KD-A: ±0.25% FS; 616KD-B: ±1% FS, 616KD: ±2% FS.
- Stability:
- ±1% FS/year.
- Temperature Limits:
- 0 to 140°F (-17.8 to 60°C).
- Compensated Temperature Range:
- 20 to 122°F (-6.67 to 50°C).
- Pressure Limits:
- 2 psig (ranges 5" w.c. or lower); 5 psig (ranges 10 to 40" w.c.).
- Thermal Effect:
- 616KD-A: ±0.02% FS/°F; 616KD-B: ±0.04% FS/°F; 616KD: ±0.06% FS/°F, includes zero and span.
- Power Requirements:
- 4-20 mA output: 10 - 35 VDC (2 wire) or 12-26 VAC (4 wire); 5V output: 10 - 35 VDC (3 wire) or 12-26 VAC (4 wire); 10V output: 13 - 35 VDC (3 wire) or 12-26 VAC (4 wire) for 616KD A and B. 16 to 36 VDC (2 or 3 wire): 20 to 28 VAC (3 wire) for 616KD.
- Output Signal:
- 4 to 20 mA or option with field selectable 0 to 10, 0 to 5, 2 to 10, 1 to 5 V.
- Zero and Span Adjustments:
- Push button.
- Loop Resistance:
- 4 to 20 mA output (DC): 0 to 1250 Ω max. Rmax = 50(VpsDC -10) Ω; 4 to 20 mA output (AC): 0 to 1200 Ω max. Rmax = 50(1.4 VpsAC -12) Ω; Voltage output: 5 KΩ minimum.
- Current Consumption:
- 24 mA max for 616KD A and B. 21 mA max for 616KD.
- Electrical Connections:
- Screw-type terminal block.
- Process Connections:
- Barbed, dual size to fit 1/8" & 3/16" (3 mm and 5 mm) ID rubber or vinyl tubing.
- Enclosure Rating:
- NEMA 1 (IP20), Tested to UL 2043 for Plenum applications.
- Mounting Orientation:
- Vertical with pressure connections pointing down.
- Weight:
- 1.8 oz (51 g).
- Agency Approval:
- CE, UL Standard 2043.
Features
- Simple calibration push-button sets back zero and span, saving time installing and over the service life
- Cost effective and compact device suitable for OEM applications where space, simplicity, and value are key
- Ranges and accuracy selection cover a wide range of applications minimizing components and determining standardizing on design
- Optional 1/8" NPT process connection allows for use with metal barbed fittings or compression fittings for use with metal tubing
- Side mounted push button zero (-A and -B models only)
Accessories
Model Number | Description | Usually Ships* | Price | Order | |
---|---|---|---|---|---|
A-618 | Protective terminal cap | Same Day | $1.90 | Order | |
![]() |
A-489 | 4" 303 SS straight static pressure tip with flange, 1/4" hose barb. | Same Day | $9.00 | Order |
![]() |
SCD-PS | 100 to 240 VAC/VDC to 24 VDC power supply. | Same Day | $36.50 | Order |
![]() |
A-360 | Aluminum DIN rail | Same Day | $11.00 | Order |
![]() |
A-302F-A | 303 SS Static pressure tip with mounting flange, for 3/16" I.D. rubber or plastic tubing. 4" insertion depth, includes mounting screws | Same Day | $11.75 | Order |
![]() |
A-480 | Plastic static pressure tip. | Same Day | $2.00 | Order |
Videos
Model Chart
EXAMPLE | 616KD | A | 00 | AT | Series 616KD-A-00-AT, Differential Pressure Transmitter, 4-20mA, range 0-1" w.c., with aluminum tag |
SERIES | 616KD | Differential Pressure Transmitter | |||
ACCURACY | A B |
0.25% FS Accuracy 1.0% FS Accuracy 2.0% FS Accuracy |
|||
RANGE | 00 01 02 03 04 05 06 07 08 10 11 12 13 14 15 50 51 57 52 53 54 55 56 58 |
0-1" w.c. 0-2" w.c. 0-3" w.c. 0-5" w.c. 0-10" w.c. 0-15" w.c. 0-20" w.c. 0-25" w.c. 0-40" w.c. 0-250 Pa 0-500 Pa 0-750 Pa 0-1250 Pa 0-2500 Pa 0-5000 Pa 0 to ±1" w.c. 0 to ±2" w.c. 0 to ±3" w.c. 0 to ±5" w.c. 0 to ±10" w.c. 0 to ±250 Pa 0 to ±500 Pa 0 to ±750 Pa 0 to ±1250 Pa |
|||
OPTIONS | AT COC FC N NIST TC V Z1 Z2 |
Aluminum Tag Certificate of Conformance Factory Calibration NPT NIST Certification (A & B only) Terminal Cover Voltage output 0 to 5, 1 to 5, 0 to 10, 2 to 10 VDC (field selectable) +/- 1%FS Zero-Deadband (Only with -A/B/C) +/- 2%FS Zero-Deadband (Only with -A/B/C) |
Product Literature
Manuals
Catalog Pages
Product Data Sheet
Approvals
Drawings
Product Reviews
Only registered users can write reviews. Please Sign in or create an account