SPECIFICATIONS
Front Panel Selectable Inputs: Thermocouple, RTD, DC voltage
or DC current.
Input Impedance:
Thermocouple - 3 Megohms min.
Voltage - 5000 ohms.
Current - 10 ohms.
RTD Current - 200 µA max.
Output: 3-15 psig (.21-1.1 kg/cm²).
Accuracy: ±1.0% of span.
Linearity: ±0.75% of span.
Hysteresis: ±0.5% of span.
Repeatability: ±0.5% of span.
Power Requirements: 100 to 240 VAC nominal ±10%, 50 to 400 Hz,
single phase; 132 to 240 VDC ±10%.
Temperature Limits: 14 to 130°F (-10 to 55°C).
Pressure Connections: 1/4" female NPT (supply and output).
Air Consumption: 0.1 scfm (.05 1/s) @ 100 psig.
Output Capacity: 4.0 scfm (1.9 1/s.)
Enclosure: NEMA 4X.
Weight: 8 lb 2 oz (3.69 kg).
|