Home Product Information Free Literature International Distribution What's New About Us Contact Us
Quick Search
Dwyer Series
IS626

Intrinsically Safe Pressure Transmitter
For use in Hazardous Locations

SPECIFICATIONS
Service: Compatible gases and liquids.
Wetted Materials: Type 316, 316L SS.
Accuracy: 0.25% full scale (includes linearity, hysteresis, and repeatability).
Temperature Limit: 0 to 176°F (-18 to 80°C).
Compensated Temperature Range: 0 to 176°F (-18 to 80°C).
Thermal Effect: ±0.02% FS/°F (includes zero and span).
Pressure Limits: See Pressure Range Table.
Power Requirements: 10 to 28 VDC.
Output Signal: 4 to 20 mA.
Response Time: 50 msec.
Loop Resistance: 0 - 900 ohms maximum.
Current Consumption: 38 mA (maximum).
Electrical Connections: 3 ft. cable or 4-pin M-12 Connector.
Process Connection: 1/4˝ male/female NPT and BSPT.
Enclosure Rating: NEMA 4X (IP66).
Mounting Orientation: Mount in any position.
Weight: 8.9 oz (252 g).
Agency Approvals: CE, UL and cUL Intrinsically Safe to UL Standard 913.

For use in Hazardous (Classified) Locations:
Class I Div. 1 Groups A,B,C,D
Class II Div. 1 Groups E,F,G
Class III Div. 1
Temperature Code: T4 @ 80°C ambient.
Install in accordance with control drawing 01-700797-00.
WARNING To prevent ignition of flammable or combustible atmospheres, disconnect power before servicing.
Use with approved safety barriers using entity evaluation.

Home
Product Information
Free Literature
International Distribution
About Us
Contact Us
Terms & Conditions of Sale
Terms of Access