Home Product Information Free Literature International Distribution What's New About Us Contact Us
Quick Search
Dwyer Series
674

Differential Pressure Transmitter
±1% FS Accuracy, Up to Six Field Selectable Ranges, 10 psid Overpressure


NEMA 4 Enclosure Shown.

SPECIFICATIONS
Service: Clean dry air or any inert gas.
Wetted Materials: Brass hose barbs, silicone.
Accuracy: ±1% FS (includes non-linearity, hysteresis and non-repeatability).
Stability: Less than 1% FS/year.
Temperature Limits: 0 to 175°F (-18 to 80°C), 10 to 90% RH, non-condensing.
Pressure Limits: 10 psid (0.69 bar).
Compensated Temperature Range: 25 to 150°F (-4 to 65°C).
Thermal Errors: ±0.0125%/°F (0.02%/°C).
Supply Voltage: 12-40 VDC.
Output: 4-20mA, 2-wire.
Zero and Span Adjustment: ±15%, non-interactive.
Response Time: 60 msec.
Loop Resistance: 1600 Ω @ 40 VDC.
Electrical Connections: Unpluggable screw terminal block.
Pressure Connections: Barbed for 1/4" O.D. 5/32" I.D. tubing.
Enclosure: Models 674-4XX: Cold-Rolled Steel, NEMA 4 (IP56); Models 674-1XX: Panel Mount.
Weight: Models 674-4XX: 1.0 lb (.45 kg); Models 674-1XX: 0.5 lb (.25 kg).
Agency Approvals: CE.

Home
Product Information
Free Literature
International Distribution
About Us
Contact Us
Terms & Conditions of Sale
Terms of Access
© Copyright 2005  Dwyer Instruments Pty Ltd All rights reserved.